Energy savings evaluation for dry-cooler equipped plants in shopping mall buildings

Energy savings evaluation for dry-cooler equipped plants in shopping mall buildings

Alessandra De Angelis*Luca Ceccotti, Onorio Saro 

University of Udine, Polytechnic Department of Engineering and Architecture, via delle scienze 208, Udine, Italy

Corresponding Author Email: 
alessandra.deangelis@uniud.it
Page: 
S361-S366
|
DOI: 
https://doi.org/10.18280/ijht.35Sp0149
Received: 
| |
Accepted: 
| | Citation

OPEN ACCESS

Abstract: 

In the present paper the possible energy savings achievable by means of dry coolers adoption in cooling plants serving shopping mall buildings has been carried out.

In these buildings, could happens that, due to internal gains caused by occupancy, lighting, and electrical devices, or because of solar radiation entering through the large skylights on the aisle, some zones have to be cooled also during the middle and the winter seasons.

The aim of this work is the evaluation of the energy saving, reachable when a water indirect free cooling system is integrated into a traditional cooling equipment in a shopping mall. Depending on outside climate conditions, the dry-cooler units could be used alternatively to cool down the refrigerant flow, or the water supplied to fan coils, achieving in such a way an indirect free cooling; so, the proposed system allows to turn off the chiller.

By means of energy simulations, electrical energy saving in different locations has been evaluated. Simulations results allowed a comparison between a traditional plant and a plant equipped with a dry-cooler. These simulations were useful to evaluate the influence of weather conditions in the dry cooler integration convenience.

Keywords: 

trnsys, energy saving, cooling, commercial mall, dry cooler

1. Introduction

The cooling energy requirements are certainly a key issue in warm climates. Large increases in building energy consumption are found in the summer, especially during the daytime, while decreases are found in the winter [1].

 These aspects are most relevant in buildings which have high volume and high internal thermal loads and a kind of buildings that have these features are the shopping malls. In these buildings, could happens that, in order to preserve the thermal comfort conditions, some zones have to be cooled also during the middle and the winter seasons.

Energy consumption in commercial buildings accounted for 31% of U.S. primary energy consumption in 2010 [2] and it is increasing directly influenced by climate change.

In fact, due to internal gains caused by occupancy, lighting, and electrical devices, or because of solar radiation entering through the large skylights on the aisle, internal gains could be higher than heat losses through building envelope. Under these conditions, the cooling installation has to be activated during the middle and the winter seasons too.

Vapour compression refrigeration systems involve high energy consumptions and environmental emissions and that makes this kind of technology unattractive. Improving the existing HVAC system is a possible way to reduce energy consumptions of energivorous buildings. Several studies about energy saving strategies regarding the HVAC systems improvement, have been carried out by different authors.

Many of them proposed to add to a traditional refrigeration equipment an evaporative cooling system.

Vakiloroaya et al. in a recent review paper [3] investigated the ability of different approaches to improve the efficiency of HVAC systems in order to obtain an HVAC energy saving. They proposed a hybrid evaporative cooling system in order to reduce the air temperature more than wet-bulb temperature of the outside air, that represents the lowest temperature DEC system can reach.

Results were compared with measured data of an existing central cooling plan of a commercial building and showed that the proposed system allows an energy saving potential up to 52% [4].

Other authors [5] studied the energy saving obtained combining a central cooling plant with a regenerative evaporative cooling system and they found that this solution is able to accomplish 15.69 % annual electricity saving of the building.

Moreover Heidarnejad et al. [6] evaluated the effectiveness of a hybrid system composed by a nocturnal radiative cooling, a cooling coil and a direct evaporative cooling. Results showed that energy saving obtained with the hybrid system is considerably higher than stand-alone direct evaporative cooling.

A combined experimental plant consisting of an IEC unit and a packaged unit air conditioner was realized and tested by Delfani et al. [7]; they found a reduction in cooling load up to 75% and a reduction in electrical energy consumption around 55% during cooling season.

Previous studies [8], carried out by the same authors, have evaluated the possible energy savings achievable by means of dry coolers adoption in heating and cooling plants serving office buildings.

The aim of this work is the evaluation of the energy saving in a shopping mall, reachable when a water indirect free cooling system is integrated in a traditional cooling equipment. The indirect free cooling system is achieved by means a dry cooler.

Depending on outside climate conditions, the dry-cooler units could be used alternatively to cool down the refrigerant flow, or the water supplied to fan coils, achieving an indirect free cooling. Under suitable weather conditions, the proposed system allows to turn off the chiller, and this results in electricity saving.

A typical shopping mall has been modeled by means of a building energy performance simulation program (TRNSYS). In this way, cooling and heating demands have been evaluated. The simulations have been carried out using weather data corresponding to northern, central and southern European cities.

Regarding the installation modeling, the technical characteristics of commercial components have been used.

By means of energy simulations, the number of hours in which the chiller could be turned off has been evaluated. Then, simulations for the traditional plant without the dry-cooler, have been carried out for each one of the considered locations, in order to evaluate the electrical energy required by the installation with and without dry-cooler. These simulations were useful to evaluate the influence of weather conditions in the dry cooler integration convenience.

2. Building Model

A rectangular double floor building with a gross floor area of 20000 m2 and a height of 4 m were considered. The total volume is 160000 m3. Fig. 1-a shows the internal layout of a building floor.

The longer edge of building is oriented along north-south axis and the entrance glass doors are on two shorter edges.

Figure 1. Floor plan for the simulated building with using destination (a), and thermal zones (b)

With reference to internal layout, shops take up perimetral and core zones and occupy 60% of the total floor area, leaving 40% of the floor area to a common zone in order to allow a suitable space for the flow of people during the peak time.

Initially, it has been modeled horizontal skylights, but in this way gains of solar radiation were very high; so, a shed roof with 12 vertical skylights, 0.70 x 2.5m, has been chosen.

Taking into account the relevant dimension of building, different thermal zones, that have the same internal load and the same heat losses through wall, were set. For each floor different zones, perimeter zones and one core zone, summarized in Fig. 1-b, were considered.

In this way it is possible to predict the thermal performance of any thermal zone in the building and the total building thermal performance is defined according to an assessment related to its thermal zones.

The model of the building, shown in Fig. 2, was created with TRNBuild module.

 

Figure 2. Sketch of the simulated commercial mall

Two different walls and two different slabs were defined:

  ♦ external wall

  ♦ inner wall

  ♦ ground floor

  ♦ middle floor

  ♦ external ceiling

The building elements properties were summarized in Table 1.

Table 1. Building elements construction details

Exterior wall

Inner wall

Material

Thickness [m]

Material

Thickness [m]

concrete

0.07

concrete

0.07

polystyrene

0.08

polystyrene

0.06

concrete

0.07

concrete

0.07

U

0.351 W/m2K

U

0.456 W/m2K

Ground floor

Roof

Material

Thickness [m]

Material

Thickness [m]

tiles

0.01

concrete

0.1

concrete

0.04

polystyrene

0.1

polystyrene

0.08

concrete

0.1

concrete

0.3

 

 

U

0.34 W/m2K

U

0.283 W/m2K

The window glazing value Uw was assumed to be 5,8 W/m2K.

Daily and hourly schedules were adopted to control the infiltration, occupation, internal gains and HVAC system. In commercial malls the main internal loads are those due to people and lights, therefore it is very important to know opening times and people turnout.

In order to carry out more realistic simulations, existing shopping malls with their opening times were considered. Shopping malls, listed in Table 2, are located at the same places chosen for the simulations.

Table 2. Opening times of existing shopping malls

City

Days

Opening times

Name

Milan

Mon-Sat

8.30-21.00

Centro commerciale piazza Lodi

Sun

9.00-20.00

Messina

Mon-Sat

9-20.30

Centro commerciale Tremestieri

Sun

9.30-20.30

Udine

Mon-Thu

9.30-20.30

Centro commerciale Città Fiera

Fri

9.30-22

Paris

Mon-Sat

10.00-20.00

Italie Deux

Sun

Closed

Berlin

Mon-Sun

9.00-21.00

Bikini Berlin

Hamburg

Mon-Sat

10.00-20.00

Europa passage

Sun

Closed

Geneva

Mon-Sat

9.00-19.00

Le Praille

Sun

Closed

Vienna

Mon-Sat

9.00-20.00

Wien Mitte

Sun

Closed

Warsaw

Mon-Sun

10.00-21.00

Wola Park

Madrid

Mon-Sat

10.00-21.00

ABC Serrano

Sun

Closed

The evaluation of electrical equipment loads was carried out according to ASHRAE Standard guidelines (Table 3) and, assuming a low load, it has been considered a value of 30 W/m2 thinking of a shop inside a shopping mall has a higher electrical load than a single shop.

Table 3. Electrical loads – Ashrae

Building

Low

 load

Medium load

High

load

[W/m2]

[W/m2]

[W/m2]

Commercial malls

32

54

97

Commercial malls (single floor)

38

65

67

Shops

11

22

43

Restaurant, dining rooms

16

18

22

Electrical load was split in a radiative part (30%) and a convective part (70%).

Thermal load of electrical equipment were calculated as product of electrical power, interval time and a coefficient depending on the day of the week; the coefficient was set to 1 during opening hours and to 0,2 during closing hours in order to account for stand-by conditions.

On zones where there are skylights, windows or entrance doors, a infiltration rate equal to 0,5 ACH (Air Changes per Hour) was imposed.

The definition of the number of people inside shopping mall was carried out according to UNI10339-2014 and, for each building, a design value of crowding index equal to 0,2 person/m2 was considered both sale zone and common zone. The peak value was scaled down based on daily and weekly schedule of occupant’s presence.

The fraction of the design value is defined as the ratio of the actual load to the peak or maximum load.

Human sensible and latent heat loads from people depend on their activity and, with reference to ISO7730, assuming a light activity for shopping mall, a load of 185 W for each person (90 sensible and 95 latent) was chosen.

3. Cooling Plant System

The cooling plant system consists of fan coil units fed with water coming from an air conditioning system based on mechanical vapor compression. This air conditioning system needs a significant amounts of electricity. The most widely used refrigeration plant for commercial building is a water-cooled condensers system, which often uses recirculation water from cooling towers.

In these systems, water leaves the water-cooled condenser and enters the top of the cooling tower, where it is sprayed over the fills and cooled to a lower temperature by means of evaporation. Thereafter it is supplied to the water-cooled condenser again.

A choice, investigated in present paper, is substituting cooling towers for dry-coolers, which have the advantage of occupying less space and of being more flexible. Moreover, when the weather conditions are suitable, water cooled by dry-coolers can be directly supplied to fan-coils, without using the chiller. A schematic layout of the refrigerant equipment is shown in Fig. 3.

Figure 3. Schematic layout of the refrigerant equipment

4. Simulations

4.1 Trnsys model

Dynamic simulation of commercial mall using three different cooling plant configurations is carried out in TRNSYS software on hourly basis.

After drawing the 3D model of the building by means of TRNSYS3D, a plug-in of Sketchup software, and defining internal characteristics and conditions of building in TRNBUILD, all the components of cooling plant are modeled in TRNSYS Studio to run the simulations for three different systems:

  ♦ cooling plant with a vapor compression system

  ♦ cooling plant with a vapor compression system combined with an indirect free cooling system (working all day long); the cooling plant can works with a traditional mode or with a free cooling mode if the external weather conditions are suitable

  ♦ cooling plant with a vapor compression system combined with an indirect free cooling system (working from 7 am to 11 pm)

TRNSYS performs cooling load calculations with transfer function method by using weather and building information data. Simulations were carried out using an ideal air conditioning system, assuming set points for cooling and heating 24 and 20°C respectively.

The TRNSYS model has been implemented using the following type:

  ♦ Building (Type 56)

  ♦ Weather data (Type 15-3)

  ♦ Fan coil (Type 600)

  ♦ Chiller (Type 666)

  ♦ Dry Cooler (Type 511)

Different climatic conditions are investigated considering ten European cities (Fig. 4):

  ♦ Hamburg (Germany)

  ♦ Geneva (Switerland)

  ♦ Madrid (Spain)

  ♦ Messina (Italy)

  ♦ Milan (Italy)

  ♦ Munich (Germany)

  ♦ Paris (France)

  ♦ Prague (Czech Republic)

  ♦ Warsaw (Poland)

  ♦ Wienn (Austria)

 

Figure 4. European cities considered in simulations

In order to choose cities with different weather conditions, the Cooling Degree-Hours, Base J0 (CDH_J0), has been considered as discriminating factor; the index is proposed by ASHRAE [9] and is defined as:

$C D H_{-} \vartheta_{0}=\sum_{j=1}^{N}\left(\vartheta_{e}-\vartheta_{0}\right)$ for $\vartheta_{e}-\vartheta_{0}>0$

where Je is the hourly dry bulb temperature, N is the number of hours for entire year and J0 is the base temperature.

According to the design value of the internal air temperature, suggested by International Standards [10] for the summer period, a base temperature equal to 26°C has been used to evaluate the parameter CDH_26. Fig. 5 shows the CDH_26 for the different cities considered.

 

Figure 5. CDH_26 for the different cities considered

4.2 Chiller performance

The chiller has been considered as a high performance centrifugal compressor chiller with condenser cooled by water. It has been modeled by means of TRNSYS Type 666, which allows to take into account the influence of external climatic conditions over the chiller performance. Figure 6 shows the variation of EER values for different chilled water temperatures, varying the cooling water temperature.

 

Figure 6. EER trend over cooling water inlet temperature for different outlet temperatures of the chilled water

4.3 Free cooling

Cooling plant have to work in free cooling mode only under suitable conditions, that are:

  ♦ temperature gradient between internal air and external air have to be greater than 10 K;

  ♦ fan-coils have to be switched on.

In particular the first condition takes into account that water have to pass through two heat exchangers and therefore the temperature difference have to be greater than 10 K.

5. Simulation Results

As it is reasonable to expect, during the winter the cooling plant works mainly in free cooling mode, whereas during the summer the plant works mainly in traditional mode, but the amount of free cooling hours depends on the weather conditions and therefore on the locations.

In fig. 7 it is shown a comparison of the chiller working hours HC in two different situations, when the cooling plant doesn’t employ free-cooling and when the cooling plant works in a free-cooling mode.

 

Figure 7. Comparison of the chiller working hours HC in two different situations, in free cooling mode and in traditional mode

Obviously, the reduction of working chiller hours could not be a meaningful parameter to evaluate benefit of employing free-cooling and for this reason the energy consumptions of two scenarios are considered.

The energy consumptions has been evaluated in both cases, with and without free-cooling mode, and in figure 8 the reduction of electrical energy in percentage for all considered locations is summarized.

 

Figure 8. Reduction in percentage of electrical energy consumptions for the considered locations

Above all, as shown in fig. 8, in some cities the amount of the electrical energy saving is quite considerable due to suitable climatic conditions despite the good performance of the considered chiller.

Also in hot cities, the energy saving percentage reaches significant values as in Messina.

In order to highlight the influence of weather conditions on the amount of energy saving, fig. 9 shows the percentage reduction of the chiller electrical energy consumptions vs CDH_26.

Figure 9. Percentage reduction of the chiller electrical energy consumptions vs CDH26 for the considered locations

Energy saving shows a good linear dependence with the cooling degrees, leading an index correlation equal to r = 0,95.

6. Conclusions

In the present study have been investigated the advantages, in terms of energy saving, achievable by means of the integration of an indirect free cooling system in a traditional cooling plant used for a shopping center cooling.

In particular, the dry-cooler units could be used alternatively to cool down the refrigerant flow, or the water supplied to fan coils, achieving in such a way an indirect free cooling. Under suitable weather conditions, the proposed system allows to turn off the chiller and allows to save electrical energy.

A commercial mall with both a dry-cooler equipped cooling plant and a traditional one has been simulated by means of TRNSYS, and the results have been compared in terms of number of hours in which the chiller could be turned off and amount of energy saving. Different weather data (northern, central and southern European cities) have been considered for the simulations.

Simulations show that among the considered locations the city with the greatest annual energy saving amount (42.4%) is Hamburg, whereas the city with the lowest annual energy saving amount (14.2%) is Messina. As it is reasonable to expect, in cities with a colder climate there is a greater energy saving due to a lower value of the external mean air temperature; for the same reason, during the winter the proposed system is more useful.

Further investigations will be carried out taking in to account different thermal characteristics of the building envelope; a more insulated building requires a lower cooling load, which can be more likely supplied employing the external air. Moreover, it will consider the latent heat that have to be disposed of.

Nomenclature

EER

energy efficiency ratio

H

number of hours, h

U

thermal transmittance, W. m-2. K-1

$\vartheta$

temperature

Subscripts

c

chilled

C

chiller

e

external

w

window

out

outlet

  References

[1] Huang J., Gurney K.R. (2016). The variation of climate change impact on building energy consumption to building type and spatiotemporal scale, Energy, Vol. 111, pp. 137-153. DOI: 10.1016/j.energy.2016.05.118 

[2] Kelso J. (2011). Buildings Energy Data Book Energy, from http://buildingsdatabook.eren.doe.gov/

[3] Vakiloroaya V., Samali B., Fakhar A., Pishghadam K. (2014). A review of different strategies for HVAC energy saving, Energy Conversion and Management, Vol. 77, pp. 738-754. DOI: 10.1016/j.enconman.2013.10.023

[4] Vakiloroaya V., Khatibi M., Ha Q.P., Samali B. (2011). New integrated hybrid evaporative cooling system for HVAC energy efficiency improvement, IEEE/SICE International Symposium on System Integration, Kyoto, Japan, pp. 591-596. DOI: 10.1109/SII.2011.6147546 

[5] Khandelwal A., Talukdar P., Jain S. (2011). Energy savings in a building using regenerative evaporative cooling, Energy Build, Vol. 43, pp. 581-591. DOI: 10.1016/j.enbuild.2010.10.026 

[6] Heidarnejad G., Farahani M.F., Delfani S. (2010). Investigation of a hybrid system of nocturnal radiative cooling and direct evaporative cooling, Building and Environment, Vol. 45, pp. 1521-1528. DOI: 10.1016/j.buildenv.2010.01.003 

[7] Delfani S., Esmaeelian J., Pasdarshahri H., Karami M. (2010). Energy saving potential of an indirect evaporative cooler as a pre-cooling unit for mechanical cooling systems in Iran, Energy and Buildings, Vol. 42, pp. 2169-2176. DOI: 10.1016/j.enbuild.2010.07.009

[8] De Angelis A., Ceccotti L., Saro O. (2016). Cooling energy savings with dry-cooler equipped plants in office buildings, International Journal of Heat and Technology, Vol. 34, Special Issue 2, pp. S205-S211. DOI: 10.18280/ijht.34S203

[9] 2009 ASHRAE Handbook of Fundamentals (SI).

[10] ISO 7730 Ergonomics of the thermal environment - Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria, 2005.