Enhancing the Energy Efficiency of a Supercritical Thermal Power Plant Through Improved Plant Load Factor, and Optimized Performance of Auxiliary Equipment

Enhancing the Energy Efficiency of a Supercritical Thermal Power Plant Through Improved Plant Load Factor, and Optimized Performance of Auxiliary Equipment

Naveen Kumar Gavirineni Edison Gundabattini*

School of Mechanical Engineering, Vellore Institute of Technology (VIT), Vellore-632 014, Tamilnadu, India

Department of Thermal and Energy Engineering, School of Mechanical Engineering, VIT, Vellore-632 014, Tamil Nadu, India

Corresponding Author Email: 
edison.g@vit.ac.in
Page: 
177-187
|
DOI: 
https://doi.org/10.18280/ijdne.170203
Received: 
11 September 2021
|
Revised: 
25 November 2021
|
Accepted: 
3 December 2021
|
Available online: 
27 April 2022
| Citation

© 2022 IIETA. This article is published by IIETA and is licensed under the CC BY 4.0 license (http://creativecommons.org/licenses/by/4.0/).

OPEN ACCESS

Abstract: 

This paper analyzes the 660 MW supercritical thermal power plant design data, operation data, and various improvement strategies of all significant auxiliary equipment at various plant load factors. The effects of the plant load factor, auxiliary equipment performance and multiple properties of coal on equipment performance are discussed here. It is observed that the operation of the supercritical thermal power plant, at the maximum continuous rating, reduces the specific auxiliary power from 5.95% at 65% Plant load factor to 4.76% at 100% Plant load factor. Hence, there is a reduction in auxiliary power of total equipment by 68.80 MU/year. Also, due to the reduction of auxiliary power, CO2 emissions reduce to 65,300 tonnes, SO2 emission reduces to 4.752 tonnes, and NOx emission reduces to 2.898 tonnes. This paper discusses and analyzes the optimization of the process, optimization of excess air, improving energy efficiency measures for individual equipment, and controlling furnace ingress. Analysis indicates the increase in plant capacity and reduction in the auxiliary power by 0.8-1.2% of gross energy generation and also a release of an additional power 7.85 MW/hour to the concerned grid.

Keywords: 

energy efficiency, plant load factor, coal consumption, flue gas, boiler feed water, excess air ratio, coal analysis, auxiliary power, CO2 emission

1. Introduction

Thermal power plants are the measured sources of energy for the production of electrical power, and they generate different pollutants in the environment. Ecological effluence may be lessened by either minimizing the energy consumption or by generating high-efficient energy. In power plants some part of the energy being consumed by different auxiliary types of equipment. The auxiliary power is different for diverse plant sizes from 20 MW to 660 MW plants, varied between 13-4.75%. The Estimated auxiliary power used in 660 MW thermal power plants is 31.3 MW/hour; this generates CO2 emission by 751.2 t/d. Thermal power plant’s obtainability fundamentally depends on the availability of fuel, water facility, auxiliary systems, ash disposable stations, load dispatching centers and operation and maintenance reliability. There are so many reasons that auxiliary power consumption in India is higher than the other developed countries. Those are excessive feedwater flow, excessive steam flow, ineffective drives, deficiency of maintenance of apparatus, poor coal quality, internal leakage of equipment, lack of technology up-gradation, oversizing of equipment, and usage of unproductive control systems. Reduction in the auxiliary power by 0.5% may add 28.38 MU of additional power into the grid and 26,963 t/y CO2 emissions could be reduced.

Supercritical once through units gives the maximum plant efficiency due to less losses from the boiler like unburnt carbon losses, dry flue gas losses, less moisture loss in combustion air and radiation losses and generates fewer pollutants than other subcritical and critical technology-based plants. Figure 1 shows the schematic of the 660 MW plant. In many countries, the vastly fluctuating grid frequency due to earthquake, physical attack, cyber attack, operations error, tsunamis, regional weather, ice storms, floods, space weather and other electromagnetic threats, hurricanes or tropical cyclones, wildfire, drought etc. This compels power units with superior part-load efficiency to realize greater economic power generation. Supercritical once through drum-less units are very useful for part load generation. Figure 2 shows the detailed process diagram and equipment.

1.1 Auxiliary power improvement

Bhatt and Mandi's [1] study indicated that the auxiliary power increases as gross energy generation (GEG) increase at full load conditions. They have identified the influencing parameters such as coal quality, excess steam flow, internal leakages, and inefficient drivers. Harley et al. [2] had studied bowl mills in pulverized coal boilers, at higher fineness (below 75 microns) power consumption of the mill is more and some carbon molecules escape from the furnace to increase carbon unburnt in fly ash. At low fineness (above 75 microns) power consumption of the mill is less than the designed values by adjusting rollers. Bhowmick and Bera [3] had studied the Induced draft performance, they had proved that Induced draft fan performance reduced due to over-design and older design (old electrostatic precipitator). Mandi et al. [4] studied the energy efficiency methods of boiler feed water pump in 210 MW thermal power plant. Their study indicated that the auxiliary power is reduced when the pump operated at 100% plant load factor. Also, the absence of re-circulation reduced the auxiliary power of the boiler feed water pump. Kumar and Rao [5] had studied the auxiliary power consumption of the total plant. Around 8% of energy generation from the plant was used to run the auxiliary equipment, and 30% for the boiler feed pump. Saha and Chatterjee [6] had compared the Indian auxiliary power consumption to other countries. They had concluded that Indian power generation units auxiliary power depletion are upper-sided due to low plant load factor, the higher ash content in coal, more steam flow, and feedwater flow consumption, lack of knowledge in the operation of utilities, design defects, etc. Adate and Awale [7] had studied boiler feed pump auxiliary power consumption and various factors affecting the auxiliary power consumption of boiler feed pump. They had concluded that the auxiliary power consumption of the feed pump could be decreased by enhancing the plant load factors. Raval and Patel [8] had studied different auxiliary power consumption and different improvement methods. They had studied in detail pumps and compressors, as these two are main auxiliaries that consume maximum power from the generation. Tsang [9] had experimented on impeller trimming (reduce the size of the impeller) of centrifugal pump. He had concluded that more trimming of impeller caused misalignment of impeller and casing. Chikkatur and Sagar [10] had done different studies about ash percentages in different coal, mill performance, and pollution generation. They concluded that 50% ash content in coal mill could increase power by 7.2% than the designed power.

1.2 Plant load factor improvement

Mandi and Yaragatti [11] had studied energy efficiency on 210 MW coal-fired power plants and concluded that the operation of the plant with improved PLF reduces the specific auxiliary power. Mandi and Yaragatti [12] had done energy-saving procedures in a 210 MW coal-fired power plant and concluded that the operation of the plant at enhanced PLF condensed the auxiliary power, net auxiliary power, and CO2 emission. CEA [13] had experimented on power plants with different plant load factors. Results indicated that by using supercritical and ultra-supercritical power plants, the plant load factor was improved and simultaneously specific auxiliary power was also decreased. Gomez [14] had studied rotary air preheater in a 210 MW coal-fired thermal power plant. He had done a detailed study in primary and secondary air heat extraction from flue gas. He had concluded that due to high pressure developed by PA and SA than flue gas, there was air leakage through APH that increased the gas flow and loading of ID fan. Sathyanathan and Mohammad [15] had studied the carbon percentage in both fly ash and bottom ash. They had found that fly ash combustibles depend on proximate analysis and GCV of coal, whereas bottom ash combustibles depend on coal particle size (50 mesh particles).

Figure 1. Line diagram of 660 MW Supercritical thermal power plant [1]

Figure 2. A 660 MW supercritical power plant schematic representation [16]

1.3 Optimization of pollution levels

Krol and Oclon [17] had studied the performance improvement prices and CO2 emission prices. They concluded that CO2 emission and fuel cost had a strong influence when coal handling plants connect with condensing turbines at low pressure. Javadi et al. [18] experimented on a 500 MW combined cycle power plant for the optimization of CO2 emission, system exergy efficiency, and energy cost to reduce the heat rate. Manzolinia et al. [19] had worked in the STEPWISE H2020 project and the SEWGS technology integrated with Iron and steel plant to know CO2 emission levels. They concluded that the SEWGS technology has enhanced steam consumption that increases energy. Kumar et al. [20] had studied coal thermal power plants in terms of emission taxation and used linear programming-based data envelopment analysis (DEA) to estimate boiler efficiency. Chen [21] had examined the changes in productivity from the regulations of the environment to control the CO2 emission in thermal power plants. They concluded that measuring productivity advancement by shadow pricing is more than the actual trading price of CO2. Liu et al. [22] had studied different environmental and pollutions issues from thermal power plants in China, they have concluded that in China thermal power plants releasing greater emissions than other sectors. Lysko et al. [23] had analysed the various emissions generations, equipment-wise auxiliary power consumption, station auxiliary power consumption, operation reliability. They had proved that CO2 emission production is equivalent to coal consumption in the plant.

1.4 Energy efficiency improvements

Mahmoudi et al. [24] had identified approaches such as multivariate data analysis to improve the boiler performance and to decrease different emissions relating rate to the atmosphere. Joskow and Schmalensee [25] had analysed the thermal efficiency and consistency of electric generating units with coal burning, they had concluded that an increase in the steam pressure of generating units had led to advances in thermal efficiency. Kumar and Rao [26] had listed the various parameters like coal flow, feedwater flow, steam flow, airflow, excess air ratios, boiler, and turbine operation. They concluded that heat loss due to hydrogen is more than other heat losses. Franco and Casarosa [27] had explored the possibilities to increase the combined cycle plant efficiency. Results indicated that the hot reheat steam generator achieves 60% by using regenerator turbine exhaust gas temperature. Mandi et al. [28, 29] had studied the air-cooled and water-cooled condenser and cooling tower in a water-cooled condenser. They had concluded that with the less cooling tower makeup water the heat exchanger capacity of the condenser could be increased. Srinivas [30] had studied the dual pressure heat recovery steam generator (HRSG). He has concluded that optimization of combustion system possible at a temperature of 1400℃ with turbine blade cooling technology.

In this paper, we have analyzed a 660 MW supercritical thermal power plant considering various parameters viz. different plant load factors, different coal properties, and improving energy efficiency measures for equipment. We have also analyzed various methods to improve auxiliary power improvement of individual equipment like various boiler losses; excess air optimization techniques on different coal samples consequently studied the coal consumption and different emission levels generation from the plant.

2. Plant Load Factor (PLF)

The plant load factor is the ratio of average load generation to the peak load in a particular period. This is the degree of the output of a power plant in comparison to the maximum output [5]. Some of the power plants are operating their load at a low plant load factor that causes high auxiliary power consumption, increase coal consumption, and emissions. There is a close relationship between plant load factor and generated output, and these two are directly proportional to both Boiler output and turbine output. Boiler output i.e., steam generation depends on airflow, flue gas flow, coal flow, feedwater flow, condensate flow [18], and pressure gain across fans and pumps. Similarly, turbine output i.e., power generation depends on condenser vacuum, steam pressure, steam flow, and steam enthalpy. Power consumption on individual drives depends on equipment running load if the equipment running at full load specific auxiliary power reduces [20].

Lower PLF lessens the generation of power and also reduces the feedwater flow, condensate flow, air flows, and flue gas flow. Lower plant load factors are also due to specific steam consumption (ratio between steam flows in t/h to GEG in MW), specific fuel consumption (ratio between fuel consumption in t/h to GEG in MW), and specific energy consumption (ratio between electrical power consumption in MW to the feed/condensate water consumption in tones). The equation of variation in fluid flow in second-order polynomial with plant load factor:

Fluid flow $=\mathrm{A}_{0}+\mathrm{A}_{1} * \mathrm{PLF}+\mathrm{A}_{2} * \mathrm{PLF}^{2} \mathrm{t} / \mathrm{h}$

The deviation of fluid flow with different PLF’S given in Figures 3-7. Let A0, A1, A2 are coefficients, and standard deviation R2, Table 1. The stable levels of various flows are more than 99% as shown by the Polynomial second-order curve-fit.

Figure 3 shows the comparison of operating feed water flows with design feedwater flow, at 100% PLF as per the supplier recommendation 1771 t/h but in the actual feed, water flows consumption of boiler 1810 t/h. This is due to the loss of steam to the atmosphere through safety valve passing, steam purge valve passing, heater drains passing, etc. The deviation of feedwater flow range of 3-40 t/h.

Table 1. Different fluid flows fit curve values with PLF (50-100%) at 660 MW plant

S.NO

Equipment

X-axis

Y-axis

Constant(A0)

Constant(A1)

Constant(A2)

Standard, R2

1

ID Fans

PLF's

Flue Gas Flows

679.106

-4.151

0.176

0.984

2

FD Fans

PLF's

Secondary Air Flows

450.309

17.240

-0.011

0.987

3

PA Fans

PLF's

Primary Air Flows

292.388

-2.468

0.044

0.989

4

Mills

PLF's

Coal Flow

-6.774

4.415

-0.002

0.968

5

BFP

PLF's

Feed Water Flow

416.236

15.928

0.021

0.996

6

CEP

PLF's

Condensate Water Flow

-0.272

0.011

0.003

0.995

Figure 3. Comparison of Design VS Operating feed water flows at different PLF’S

Figure 4. Comparison of Design VS Operating condensed water flows at different PLF’S

Figure 5. Comparison of Design VS Actual flue gas flows at different PLF'S

Figure 6. Comparison of Design VS Operating Primary Air flows at different PLF’S

Figure 4 shows the comparison of operating condensate water flow with design condensate water flow, at 100% PLF as per the supplier recommendation 1474 t/h whereas the condensed water flow consumption of boiler is 1512.37 t/h. This is due to the loss of steam to the atmosphere through the LP heater drain passage. The deviation of feedwater flow is in the range of 38-70 t/h.

Figure 5 shows the comparison of actual flue gas flow with design flue gas flow. Flue gas flow at 100% PLF, as per the supplier recommendation, is 2524.5 t/h whereas the actual flue gas flow from the boiler is 2810 t/h. This is due to the loss of flue gas through ducting system and loss through the rotary air preheater.

Figure 6 shows the comparison of actual PA flow with design PA flow; at 100% PLF as per the supplier recommendation design PA flow is 576.77 t/h whereas the actual PA flow supplies to the boiler are 610.2t/h. This is due to the loss of air through the rotary air preheater.

Figure 7 shows the comparison of actual SA flow with design SA flow, at 100% PLF as per the supplier recommendation design SA flow is 1501.4 t/h whereas the actual SA flow supplies to the boiler 1782.8 t/h. This is due to the loss of air through the rotary air preheater.

Figure 7. Comparison of Design VS Operating Secondary Air flows at different PLF’S

Figure 8. Comparison of Design VS Operating Coal flows at different PLF’S

Figure 8 shows the comparison of actual coal flow with design coal flow, at 100% PLF as per the supplier recommendation design coal flow is 425 t/h whereas the actual coal flow supplies to the boiler 445 t/h. This is due to the loss of boiler performance and increase of turbine heat rate.

2.1 Deviation in fluid flow

Fluid flow varies according to different loads. The boiler manufacturer provides values of the fluid flow for different loads (design data), but in running conditions, there may be a deviation from the design conditions of the plant.

Deviation in fluid flow $\frac{\left(m_{\mathrm{r}}-m_{\mathrm{o}}\right) * 100 \%}{\left(m_{\mathrm{r}}\right)}$

where, mr= Fluid flow operation from BFP, Primary airflow from PA fans, Condensate flow from CEP, Secondary airflow from FD fans, Coal flow from mills, flue gas flow from ID fans; operating = At full load 660 MWexact Fluid flow from BFP, Primary airflow from PA fans, Condensate flow from CEP, Secondary airflow from FD fans, Coal flow from mills, flue gas flow from ID fans.

In a 660 MW power plant under full load conditions, the deviation of fluid flows is polynomial curve-fitted in the second-order derivative, Figure 9. From the deviation of fluid flows data (curve-fitted in second-order derivations), three constants and standard deviation could be found out.

Deviation in Fluid flow $=\mathrm{B}_{\mathrm{o}}+\mathrm{B}_{1} * \mathrm{PLF}+\mathrm{B}_{2} * \mathrm{PLF}^{2} \%$

where, B0, B1, B2 coefficients, and R2 standard deviation for all major equipment. The curve-fit second-order polynomial of variation of different flows given in Table 2. The values are in the range of 0.868 – 0.968. The value of the curve-fit for flue gas flow is 0.868, primary airflow is 0.968, secondary airflow is 0.953, coal flow is 0.957, feedwater flow is 0.926, and condensate flow is 0.948.

Figure 9. Deviation of different fluid flows with PLF (50-100%) at 660 MW plant

Table 2. Deviation of different fluid flows curve-fit values with PLF (50-100%) at 660 MW plant

S.NO

Equipment

X-axis

Y-axis

Constant(B0)

Constant(B1)

Constant(B2)

Standard, R2

1

I.D Fans

PLF's

Flue Gas Flows

-123.910

16.968

-0.090

0.868

2

F.D Fans

PLF's

Secondary Air Flows

62.124

-6.759

0.048

0.953

3

P.A Fans

PLF's

Primary Air Flows

-91.444

0.807

-0.003

0.968

4

Mills

PLF's

Coal Flow

-63.975

0.707

-0.004

0.957

5

B.F.P

PLF's

Feed Water Flow

-138.078

3.340

-0.027

0.926

6

C.E.P

PLF's

Condensate Water Flow

41.722

5.278

-0.035

0.948

Following components and factors affect the plant load factor:

  1. ID Fans: Selection of under-capacity drive, impeller damage, leakages found from fan ducts
  2. FD Fans: High/low wind box pressure maintenance, selection of under capacity, impeller damage, leakages found from ducts
  3. PA Fans: Maintaining of low differential pressure across the fan, selection of under capacity, impeller damage, leakages found from ducts
  4. Inaccessibility of Mills, PA, and SA fans
  5. Poor coal quality: high moisture and ash content in coal reduce mill capacity, overloading of ID fans, and Performance of ESP could be reduced.
  6. CW pump: Vacuum reduces due to insufficient cooling water in the condenser
  7. Overloading of ID fans, FD, and PA fans due to air leakage in APH
  8. BFP and CEP: Reduced differential pressure across strainer and passing in recirculation valve
  9. HP and LP heater: Reduced hydro-dynamic pressure drop across the circuit
  10. Inadequate coal supply
  11. Unplanned outages
  12. Less demand from the grid side.
3. Auxiliary Power

The initial starting of the plant requires power and is supplied by external grids on a chargeable basis. The power could be distributed to equipment by station transformer which is located adjacent to the GT. Once power generation starts, power is available for running the equipment, this power is called unit auxiliary power. This power is tapped from the unit auxiliary transformer. The unit auxiliary power transformer supplies power to all equipment. The auxiliary power could be divided into two groups, in-house auxiliary power and Out-door auxiliary power or general auxiliary power.

The In-house auxiliary power equipment: Forced draft fans (FD), Boiler feed pumps (BFP), Primary air fans (PA), Induced draft fans (ID), Coal mills (pulverizes), and Condensate extraction pumps (CEP). Out-door or general auxiliary power is the power used for general tools such as auxiliary cooling water pumps (ACW), Circulating water pumps (CW), Demineralised water pumps, ash water pumps, Conveyors, Belts, Crushers, Common lighting available in the plant. Table 3 shows the major auxiliary power details.

Some power is always needed for the running of equipment; hence the specific power is defined as the ratio of power consumed by the equipment at motor terminals to the maximum generation.

SpecificAuxiliarypower $=\frac{(\mathrm{Pm} * 100)}{(\mathrm{Pl} * 100)}$

where, Pm = Measured power input to the motor, Pl= Measured P.L.F.

The specific auxiliary power of HT equipment is polynomial curve-fitted and is second-order concerning PLF.

Auxiliary Power (A.P) = 8.9*10-5 *PLF2-0.098162*PLF + 17.66993%

Table 4 shows the standard deviation for the second-order polynomial curve-fit is 0.978. It is showing a confidence level is more than 97%. It is appropriate and the scatter of data for the given units is within 2-3%.

Deviation in Auxiliary power $=\mathrm{C}_{0}+\mathrm{C}_{1} * \mathrm{PLF}+\mathrm{C}_{2} * \mathrm{PLF}^{2} \%$

where, C0, C 1, C 2 coefficients and R2 standard deviation given for all major equipment. The curve-fit second-order polynomial of variation of different specific auxiliary power is given in Table 4.

Deviation in Auxiliary power at various PLF’s in 660 MW.

unit $=\frac{\left(A P_{\mathrm{r}}-A P_{\mathrm{o}}\right) * 100 \%}{\left(A P_{\mathrm{r}}\right)}$

where, APr is the rated/design auxiliary power in kW, APo is the present operating auxiliary power in kW. The polynomial curve-fit for various specific auxiliary power with different PLF’s is in the range of 0.88-0.99% shown in Table 5. The attainable efficiency level of ID Fan is 88.07%, but in reality, it is low due to air leakage through APH, air enters through ducts, and hydrodynamic pressure drop.

In a 660 MW power plant under full load conditions, the deviation in different auxiliary power consumption and the deviation in auxiliary power is polynomial curve-fitted in the second-order derivative, Figure 10. From the deviation in auxiliary power consumption data (curve-fitted in second-order derivations), three constants and standard deviation could be found out.

Deviation in Auxiliary power of equipment $=\mathrm{D}_{\mathrm{o}}+\mathrm{D}_{1} * \mathrm{PLF}+\mathrm{D}_{2} * \mathrm{PLF}^{2} \%$

where, D0, D 1, D 2 coefficients, and R2 standard deviation given for all the major equipment. The curve-fitted second-order polynomial of variation of different specific auxiliary power is given in Table 6.

Figure 10. Deviation of different equipment auxiliary power consumption with PLF (50-100%) at 660 MW plant

Table 3. Details about the primary auxiliary power equipment (in-house)

S.No

Equipment

No. of equipment (Running/ Standby)

Equipment Description

Speed,

 rpm

Efficiency,

%

Motor Rating, kW

Fluid flow

1

ID Fan

2+0

Axial Reaction with Variable Blade pitch control

745

84.5

4200

710

2

FD Fan

2+0

Axial Reaction with Variable Blade pitch control

990

84.5

1700

280

3

PA Fan

2+0

Axial Reaction with Variable Blade pitch control

1490

87.5

3750

220

4

Pulverizer

5+1

Bowl mill

989

82.5

1000

85

5

BFP

2+1

Horizontal, centrifugal type with barrel casing

2900

85.7

10859

1439.8

6

CEP

1+1

Vertical, multistage

1480

94

1040

849

7

CW Pumps

2+1

Vertical, self-water cooling

330

89.78

2600

29330

8

ACW Pump

2+1

Horizontal, centrifugal, multistage

983

86.25

110

2275

Table 4. Different auxiliary power curve-fit values with PLF (50-100%) at 660 MW plant

S.NO

Equipment

X-axis

Y-axis

Constant1

Constant2

Constant3

Standard, R2

1

Auxiliary power Design

PLF's

Auxiliary power in MW

8.6325

-0.10337

0.0004

0.98513

2

Auxiliary power Operation

PLF's

Auxiliary power in MW

8.81244

-0.09289

0.00035

0.97863

Table 5. Different auxiliary power values at different P.L.F

S.No

Equipment

X-axis

Y-axis

Constant (C0)

Constant (C1)

Constant (C2)

Standard R2

1

ID Fans

PLF's

ID Fan Power Consumption

0.6241

0.0303

-0.0001

0.8807

2

FD Fans

PLF's

FD Fan Power Consumption

0.7038

-0.0014

0.0001

0.9798

3

PA Fans

PLF's

PA Fan Power Consumption

0.5738

0.0178

0.0000

0.9856

4

Mills

PLF's

Mill Fan Power Consumption

0.0080

0.0065

0.0000

0.9754

5

CEP

PLF's

CEP Fan Power Consumption

0.0958

0.0112

0.0000

0.9947

Table 6. Deviation of different auxiliary power curve-fit values with PLF (50-100%) at 660 MW plant

S.NO

Equipment

X-axis

Y-axis

Constant(D0)

Constant(D1)

Constant(D2)

Standard, R2

1

ID Fans

PLF's

I.D Fan Power Consumption

-0.734

0.015

0.003

0.975

2

FD Fans

PLF's

F.D Fan Power Consumption

-0.744

0.022

0.003

0.976

3

PA Fans

PLF's

P.A Fan Power Consumption

-0.878

0.034

0.008

0.996

4

Mills

PLF's

Mill Fan Power Consumption

-0.046

0.005

0.002

0.999

5

CEP

PLF's

C.E.P Fan Power Consumption

0.261

0.000

0.009

0.865

Table 7. Different specific energy consumption values at different PLF

S.NO

Equipment

X-axis

Y-axis

Constant(E0)

Constant(E1)

Constant(E2)

Standard, R2

1

ID Fans

PLF's

SEC of ID fans

0.5459

-0.05823

0.000852

0.728

2

FD Fans

PLF's

SEC of FD fans

0.6264

-0.0821

0.000628

0.952

3

PA Fans

PLF's

SEC of PA fans

0.7682

-0.2258

0.000232

0.982

4

Mills

PLF's

SEC of Mills

1.2568

-0.1235

-0.000982

0.956

5

CEP

PLF's

SEC of CEP

0.6282

-0.2185

0.000462

0.889

The specific energy consumption for individual equipment as:

Specific energy consumption $=\frac{\text { Equipment power }}{\text { Feedwaterflow }} \mathrm{KW} /$ ton

The changes of specific energy consumption of all equipment are a second-order polynomial with different PLF’s:

Specific energy consumption $=\mathrm{E}_{\mathrm{o}}+\mathrm{E}_{1} * \mathrm{PLF}+\mathrm{E}_{2} * \mathrm{PLF}^{2} \%$

where, E0, E 1and E2 are coefficients and R2 is the standard deviation for all HT auxiliary equipment, Table 7.

The polynomial curve-fit values of standard deviation are in the range 0.728-0.982. The achievable efficiency levels for ID fan are 72.8%, for CEP is 88.9%, for FD fan is 95.2%, for Mill is 95.6%, etc. But in reality, the values are less due to incombustible air enters through APH and ducts which do not take part in the combustion. This air reduces the capacity of the ID fan.

The performance test was conducted on 2 units of 660 MW units. Two units were having a common station transformer where the station loads were distributed and having the same equipment such as ID Fans, BFP, PA Fans, FD Fans, and CEP, etc. Performance tests were conducted on Boiler and Turbine from PTC 4.1 and PTC 6.1. Blended coal having a 70:30 proportion was used as an input to the Boiler. The test was conducted for nearly 3 hours on full load. During the test period, the blowdown, soot blowing, and equipment changeover were halted to obtain an accurate result.

3.1 Detailed study on the HT- In-house auxiliary equipment

  1. Induced draft fans are used to send flue gas from the furnace to the atmosphere and uphold negative draft inside the furnace (-200 to -220 Pa) consuming 0.64% of GEG at maximum continuous rating (MCR) conditions. This is equivalent to 2.23 tones of coal consumption and releases 2.09 tones of CO2 emissions, 18.39 kg of SO2 and 3.24 kg of NOx.
  2. Forced draft fans supply air to the furnace through a wind box for effective combustion. Total 1501 tones of air supplied to furnace. The specific power consumption used for FD fans 0.26% of GEG at MCR conditions i.e., equivalent to 1.01 tones of coal consumption and release 1 ton of CO2 emission, 12.22 kg of SO2,7.40 kg of NOx.
  3. Primary air fans supply primary air to the mill to lift pulverized coal which is powdered form, from mill mixing of both Primary air and coal powder goes to the furnace for combustion. Nearly 576 tones of air go to the furnace with coal powder at MCR. The specific power consumption for PA fans 0.57% of GEG - corresponding values of 2.325 tones of coal consumption and release 2.208 tones of CO2 emission, 27 kg of SO2, and 16 kg of NOx.
  4. Mills are installed to provide the pulverized coal to the furnace for combustion. The specific auxiliary power for mill 0.15% of GEG -corresponding values of 620 kg of coal consumption/mill and release 589 kg of CO2 emission,7.2 kgs of SO2, and 4.38 kgs of NOx.
  5. Condensate extraction pumps draw water from a hot well and send it to the deaerator through LP heaters. The specific auxiliary power used by Condensate extraction pump for 0.16% of GEG at MCR condition i.e., equivalent to 644.8 kg of coal consumption and release 612.56 kg of CO2 emission,4.64 kg of SO2, and 2.824 kgs of NOx.
  6. Cooling water pumps draw water from the sea and sent to condenser for condensate cooling purpose. The specific auxiliary power used by the pump 3.93% of GEG at MCR condition i.e. equivalent to 1612 kg of coal consumption and release 1531.4 kg of CO2 emission,11.606 kgs of SO2, and 7.060kgs of NOx.
  7. The total coal consumption for auxiliary is 19.027 tones which is the equivalent release of CO2 emission 18.075 tonnes,136 kg of Sox and 86 kgs of NOx.
  8. The auxiliary power is affected by the PLF of power units. The auxiliary power rises when PLF decreases, and it would increase when PLF increases. The total specific auxiliary power changes are curve-fitted with a second-order polynomial equation with PLF.
4. Results and Discussion

4.1 Component parameters to improve the plant load factor of 660 MW thermal power plant

The PLF improvement mainly depends on the capacity of all HT auxiliary equipment like ID fan, FD fan, PA fan, BFP, CEP, etc. There are few improvement methods to increase the performance of HT auxiliary equipment for increasing the plant load factor of 660 MW supercritical thermal power plants. Some of the methods are discussed here.

4.2 Induced draft fans

ID fan performance could be improved by improving the following factors listed here:

a) I.D fan capacity increases by reducing flue gas flow, this depends on the calorific value and ash content of coal. Always low ash content and higher calorific value of coal are preferable for 660 MW units. Here consider four different coal samples with different coal proportions which are shown in Table 8. Ash in the coal reduces from 44.3% in case I to 32.1% in case IV, increase boiler efficiency from 83.93% to 86.14% [31] could reduce auxiliary power from 1000 kWh to 868.2 kWh and reduced the total auxiliary power by 0.11%. ID fan efficiency increased from 48.65% to 53.5% and reduce coal consumption to 0.5 tones. The expected average reduction in CO2 emission is 0.475 tones.

b) ID fan capacity increases by improving the efficiency of ESP from 92.5% to 98.8% by injecting NH3 into the flue gas and decreasing the erosion rate of the ID fan impeller as well.

Table 8. Various losses in Boiler according to various coal samples

   

660 MW

660 MW

660 MW

660 MW

S.No

Description

Unit

Sample1

Sample2

Sample3

Sample4

 

Proximate analysis

         

 

Fixed Carbon

%

17.3

26.4

20.1

23.28

 

Ash

%

44.3

26.65

39.7

32.0

 

Volatile Matter

%

19.0

23.6

20.0

22.0

 

Moisture- Inherent

%

19.4

23.35

20.2

22.72

 

Gross Calorific Value - A.R.B

Kcal/Kg

3630.52

3856.68

3700.82

3820.0

 

Boiler efficiency by heat loss method

I

Unburnt carbon losses

%

3.040

1.722

2.791

1.706

II

Fly ash caused sensible heat loss

%

0.251

0.134

0.207

0.155

III

Bed ash caused Sensible heat loss

%

0.492

0.279

0.436

0.335

IV

Moisture in combustion air caused loss

%

0.061

0.066

0.056

0.056

V

Moisture in fuel caused loss

%

3.385

3.819

3.441

3.738

VI

Hydrogen in fuel caused loss

%

4.382

4.166

4.446

4.146

VII

Dry flue gas caused loss

%

4.200

4.216

3.793

3.450

VII

Radiation loss

%

0.250

0.250

0.250

0.250

 

Boiler efficiency

 

83.939

85.347

84.580

86.164

4.3 Boiler feed pump (BFP)

Boiler feed pump performance would be improved by the following factors as discussed,

  1. BFP having 4 valves those are suction, discharge, leak-off balance valve, and recirculation valves. At starting of the pump recirculation valve open fully, and water flows to the deaerator. In normal running, the recirculation valve closes as per the logic of the pump. There is a huge difference between suction and discharge; some water passes through the recirculation valve. This reduced the capacity of the pump, after arranging the new recirculation valve flow passing came down to 0 flow, auxiliary power of BFP reduced by 0.10%, and CO2 emission reduced by 1085 t/y.
  2. Acid cleaning activity was performed on water tubes during overhaul time due to this auxiliary activity power reduced by 1.5%.

4.4 Mills/Pulverizers

Mill performance was improved by the following factors as discussed herewith

  1. Mill performance depends on the ash quantity of coal. If ash quantity decreases from 44.3% to 32.1% shown in Table 8, mill power is too reduced from 1000 kW to 868.2 kW and 0.01% of the overall auxiliary power is reduced from gross. Hence, there is 365 tones of coal saving and also reduced CO2 emission by 346 t/y.
  2. Coal coming from the pulverizer is in the shape of microns like talcum powder. Nearly 70% of the pulverized coal passthrough 200 mesh as per the design. An 80% pulverized coal could raise the power consumption by 6% and the finer coal would escape from furnace to secondary zone causing unburnt carbon in fly ash. Coarse pulverized heavier coal particles drop in the furnace forming a clinker.
  3. Combustion chamber temperature has to be maintained by a controlled steam purging valve to keep the mill temperature at normal value i.e., 70-75℃ to avoid blasting of the mill.
  4. The use of high Chrome ball ring segments and rollers could increase the life of rollers by more than 5000 hours and improved the mill performance by 3-4%.

4.5 Condensate extraction pump (C.E.P)

Condensate extraction pump performance was improved by the following factors:

  1. Always open balance leak offline to Deaerator for the avoidance of abnormal vibrations to damage the pump.
  2. The inlet valve is opened fully to avoid the throttling of the pump as it would increase the auxiliary power of the pump by 2%.
  3. VFD installation at the pump inlet reduced the auxiliary power of the pump to 0.05% and hence the CO2 emissions are reduced to 809 t/y.

4.6 Forced draft fans (FD)

Forced draft fans performance was improved by the following factors as discussed herewith:

  1. The pressure drop across APH was reduced from 1.05 kPa to 0.82 kPa by a thorough cleaning. And hence, the auxiliary power is reduced by 0.013%, and CO2 emissions are reduced by 65t/y.
  2. The discharge damper opening was maintained at 100% to avoid throttling losses. Throttling losses account for the reduction in efficiency by 1-2% and increased auxiliary power by 1-1.5%.
  3. Coal having a higher calorific value and low ash quantity is advisable for the boiler. This coal reduces combustion air requirement. A88t/h S.A flow reduction could reduce auxiliary power by 0.009%, also CO2 emissions are reduced by 172t/y.
  4. APH leakage reduction from 25% to 5% reduced the auxiliary power to 0.11% that reduced the CO2 emissions by 120t/y.

4.7 Primary air fans (PA)

Primary air fans performance was improved by the following factors as discussed herewith:

  1. Coal having higher a calorific value and low ash quantity is advisable for the boiler. This coal reduces combustion air requirement. A 37 t/h P.A flow reduction could reduce auxiliary power by 0.040%, also CO2 emissions are reduced by 780 t/y.
  2. During the overhaul, APH tube cleaning was done by a high-pressure jet of water. Due to this pressure drop across.
  3. APH was reduced from 9.60 kPa to 8.92 kPa, and hence, the auxiliary power is reduced by 0.035%, and CO2 emissions are reduced by 280 t/y.
  4. The discharge damper opening was maintained at 100% to avoid throttling losses. Throttling losses account for the reduction in efficiency by 1-2% and increased auxiliary power by 1-1.5%.
  5. APH leakage reduction from 25% to 5% reduced the auxiliary power to 0.025% that reduced the CO2 emissionsby380t/y.
5. Conclusions

Power plant operating at 60-100% maximum continuous rating condition, could reduce auxiliary power consumption from 5.95% to 4.76% in a 660 MW supercritical thermal power plant. At this 60-100% maximum continuous rating condition, the auxiliary power is reduced by 68.80 MU/year causing the reduction of CO2 emissions by 65,300 t/y. After optimizing the excess air and selection of low ash coal save power consumption by 97 kW/hour which is an equivalent reduction of CO2 by 0.1018 t/y and overhauling of plant equipment reduces hydrodynamic resistance of flue gas which reduces the auxiliary power by 0.11% of gross energy generation. By maintaining the performance of individual equipment, optimum excess air, and controlling furnace ingress through proper maintenance, the auxiliary power is reduced by 1.05% of gross energy. The overall reduction of auxiliary power from various methods could be 1.19% i.e., equivalent to a CO2 reduction of 65,300 t/y and added surplus power of 7.85 MW/hour into the grid through the energy conservation techniques.

Acknowledgment

We appreciate the work and technical data support by M/s. Lalitpur Power Generation Company Limited. The authors are deeply thankful to all the technical and non-technical staff members for their cooperation and kind support in conducting the experiments.

Nomenclature

Abbreviations

CO2

Carbon dioxide

SOX

Sulphur oxide

NOX

Nitrogen oxide

SO2

Sulfur dioxide

MW

Mega Watt

PLF

Plant load factor

ID

Induced draft

FD

Forced draft

MU

Million Units

SO2

Sulfur dioxide

GCV

Gross calorific value

APH

Air preheater

PA

Primary air

SA

Secondary air

ESP

Electro static precipitator

BFP

Boiler feed pump

CEP

Condensate extraction pump

HP

High pressure

LP

Low pressure

CHP

Coal handling plant

PTC

Power trading corporation

NH3

Ammonia

IGV

Internal guided vanes

VFD

Variable frequency drive

HT

High tension

LT

Low tension

GEC

Gross Energy Generation

SEWGS

Sorption Enhanced Water Gas

Acronyms

%

Percentage

R2

Standard deviation

Pm

Measured power

Degree Centigrade

kWh

Kilowatt-hour

mmwc

millimeter of the water column

t

tones

t/h

tones per hour

kW

kilowatt

k-Cal/kg

kilocalories per kilogram

kPa

kilo Pascals

$m_{\mathrm{r}}$  

rated mass

$m_{\mathrm{o}}$  

operating mass

t/y

tones per year

t/d

tones per day

  References

[1] Bhatt, M.S., Mandi, R.P. (1999). Performance enhancement in coal‐fired thermal power plants. Part III: auxiliary power. International Journal of Energy Research, 23(9): 779-804. https://doi.org/10.1002/(SICI)1099-114X(199907)23:9<779::AID-ER514>3.0.CO;2-P

[2] Harley, C., Trunkett, K.S. (2003). Coal-Gen-Improving Plant Performance with Advanced Wear Protection Technologies. Conforma Clad Inc., Albany.

[3] Bhowmick, M.S., Bera, S.C. (2008). Study the Performances of induced fans and design of new induced fan for the efficiency improvement of a thermal power plant. In 2008 IEEE Region 10 and the Third international Conference on Industrial and Information Systems, pp. 1-5. https://doi.org/10.1109/ICIINFS.2008.4798468

[4] Mandi, R.P., Seetharamu, S., Yaragatti, U.R. (2014). Enhancing energy efficiency of boiler feed pumps in thermal power plants through operational optimization and energy conservation. International Research Journal of Power and Energy Engineering, 1(1): 2-11.

[5] Kumar, C.K., Rao, G.S. (2013). Performance analysis from the energy audit of a thermal power plant. International Journal of Engineering trends and Technology (IJETT), 4(6): 2488-2490.

[6] Saha, A., Chatterjee, S. (2005). Achievements in thermal and electrical energy conservation at budge budge generating station, CSES limited. In Proceedings of National workshop on Energy Conservation for Power Engineers, at PMC, Noida, New Delhi, Organized by NTPC, pp. 32-42.

[7] Adate, N.D., Awale, R.N. (2013). Energy conservation through energy efficient technologies at thermal power plant. International Journal of Power System Operation and Energy Management, ISSN (PRINT), 2231-4407.

[8] Raval, T.N., Patel, R.N. (2013). Optimization of auxiliary power consumption of combined cycle power plant. Procedia Engineering, 51: 751-757. https://doi.org/10.1016/j.proeng.2013.01.107

[9] Tsang, L.M. (1992). A theoretical account of impeller trimming of the centrifugal pump. Proceedings of the Institution of Mechanical Engineers, Part C: Journal of Mechanical Engineering Science, 206(3): 213-214. https://doi.org/10.1243/PIME_PROC_1992_206_117_02

[10] Chikkatur, A.P., Sagar, A.D. (2007). Cleaner power in India: Towards a clean-coal-technology roadmap. Belfer Center for Science and International Affairs Discussion Paper, 6: 1-261.

[11] Mandi, R.P., Yaragatti, U.R. (2014). Control of CO2 emission through enhancing energy efficiency of auxiliary power equipment in thermal power plant. International Journal of Electrical Power & Energy Systems, 62: 744-752. https://doi.org/10.1016/j.ijepes.2014.05.039

[12] Mandi, R.P., Yaragatti, U.R. (2012). Energy efficiency improvement of auxiliary power equipment in thermal power plant through operational optimization. In 2012 IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES), pp. 1-8. https://doi.org/10.1109/PEDES.2012.6484459

[13] Performance Review of Thermal Power Stations 1999–00, 2006–07, 2007–2008, 2008–09, 2009–10, 2010–11, and 2011–12. Website: <http://www.cea.nic.in>.

[14] Gomez, J.L. (1987). Modeling of air leakages on a Tri-sector Air heater. Public Service Indiana.

[15] Sathyanathan, V.T., Mohammad, K.P. (2004). Prediction of unburnt carbon in tangentially fired boiler using Indian coals. Fuel, 83(16): 2217-2227. https://doi.org/10.1016/j.fuel.2004.05.004

[16] Adibhatla, S., Kaushik, S.C. (2014). Energy and exergy analysis of a super critical thermal power plant at various load conditions under constant and pure sliding pressure operation. Applied Thermal Engineering, 73(1): 51-65. https://doi.org/10.1016/j.applthermaleng.2014.07.030

[17] Król, J., Ocłoń, P. (2019). Sensitivity analysis of hybrid combined heat and power plant on fuel and CO2 emission allowances price change. Energy Conversion and Management, 196: 127-148. https://doi.org/10.1016/j.enconman.2019.05.090

[18] Javadi, M.A., Hoseinzadeh, S., Khalaji, M., Ghasemiasl, R. (2019). Optimization and analysis of exergy, economic, and environmental of a combined cycle power plant. Sādhanā, 44(5): 1-11. https://doi.org/10.1007/s12046-019-1102-4

[19] Manzolini, G., Giuffrida, A., Cobden, P.D., van Dijk, H.A.J., Ruggeri, F., Consonni, F. (2020). Techno-economic assessment of SEWGS technology when applied to integrated steel-plant for CO2 emission mitigation. International Journal of Greenhouse Gas Control, 94: 102935. https://doi.org/10.1016/j.ijggc.2019.102935

[20] Kumar, S., Managi, S., Jain, R.K. (2020). CO2 mitigation policy for Indian thermal power sector: Potential gains from emission trading. Energy Economics, 86: 104653. https://doi.org/10.1016/j.eneco.2019.104653

[21] Chen, B., Jin, Y. (2020). Adjusting productivity measures for CO2 emissions control: Evidence from the provincial thermal power sector in China. Energy Economics, 87: 104707. https://doi.org/10.1016/j.eneco.2020.104707

[22] Liu, X., Wang, B., Du, M., Zhang, N. (2018). Potential economic gains and emissions reduction on carbon emissions trading for China's large-scale thermal power plants. Journal of Cleaner Production, 204: 247-257. https://doi.org/10.1016/j.jclepro.2018.08.131

[23] Lysko, V.V., Moseev, G.I., Shvarts, A.L., Petrosyan, R.A., Gutorov, V.F. (1998). New-generation coal-fired steam-turbine power units (No. CONF-980426-). Illinois Inst. of Tech., Chicago, IL (United States).

[24] Mahmoudi, R., Emrouznejad, A., Khosroshahi, H., Khashei, M., Rajabi, P. (2019). Performance evaluation of thermal power plants considering CO2 emission: A multistage PCA, clustering, game theory and data envelopment analysis. Journal of Cleaner Production, 223: 641-650. https://doi.org/10.1016/j.jclepro.2019.03.047

[25] Joskow, P.L., Schmalensee, R. (1987). The performance of coal‐burning electric generating units in the United States: 1960–1980. Journal of Applied Econometrics, 2(2): 85-109. https://doi.org/10.1002/jae.3950020203

[26] Kumar, C.K., Rao, G.S. (2013). Performance analysis from the energy audit of a thermal power plant. International Journal of Engineering trends and Technology (IJETT), 4(6): 2486.

[27] Franco, A., Casarosa, C. (2002). On some perspectives for increasing the efficiency of combined cycle power plants. Applied Thermal Engineering, 22(13): 1501-1518. https://doi.org/10.1016/S1359-4311(02)00053-4

[28] Mandi, R.P., Hegde, R.K., Sinha, S.N. (2005). Performance enhancement of cooling towers in thermal power plants through energy conservation. In 2005 IEEE Russia Power Tech, pp. 1-6. https://doi.org/10.1109/PTC.2005.4524607

[29] de Backer, L., Wurtz, W.M. (2003). Why every air cooled steam condenser needs a cooling tower, Paper No.: TP03-01. In Annual Conference of CTI, pp. 10-13.

[30] Srinivas, T. (2010). Thermodynamic modelling and optimization of a dual pressure reheat combined power cycle. Sadhana, 35(5): 597-608. https://doi.org/10.1007%2Fs12046-010-0037-6

[31] Energy Auditor Books from Beauru of Energy Efficiency, ministry of power, Government of India.